Installation, Operation and
Maintenance Manual
Oil Fired Warm Air Furnace
HO-B Series Up-flow or Horizontal Model
THE INSTALLATION OF THIS FURNACE SHALL BE IN
ACCORDANCE WITH THE REGULATION OF
AUTHORITIES HAVING JURISDICTION AND NFPA
STANDARD 31 (U.S.A.) OR CSA STANDARD B139 (CAN.).
FOR YOUR SAFETY
Do not store or use gasoline or
other flammable vapors or liquids
in the vicinity of this or any other
appliance.
Oneida Royal Division
Utica, New York
Please read this manual completely
before beginning installation. These
instructions must be kept with the
furnace for future reference.
Page view 0
1 2 3 4 5 6 ... 39 40

Summary of Contents

Page 1 - Oil Fired Warm Air Furnace

29733 R2 06/01/2003 Installation, Operation and Maintenance Manual Oil Fired Warm Air Furnace HO-B Series Up-flow or Horizontal ModelTHE INSTALLAT

Page 2 - HO – B – 120 F B A 4

29733 R2 06/01/2003 10The power requirements for the HO-B Series models are: 120 VAC, 1 Æ, 60 Hz., 12A. 5-ton models: 120 VAC, 1 Æ, 60 Hz., 16A. Ac

Page 3

29733 R2 06/01/2003 11The furnaces may be installed with a one-pipe system with gravity feed or lift. The maximum allowable lift on a single line sy

Page 4

29733 R2 06/01/2003 12CHECK THE ALIGNMENT OF THE COMBUSTION CHAMBER AND OIL BURNER BEFORE FIRING. IT IS POSSIBLE FOR THE COMBUSTION CHAMBER TO SHIFT

Page 5 - HORIZONTAL INSTALLATION

29733 R2 06/01/2003 13Figure 6: Test port location for smoke test vertical. PROCEDURE: Start the burner and allow it to run at least ten minutes.

Page 6 - 5. COMBUSTION AIR

29733 R2 06/01/2003 14 IF THE FURNACE FAILS TO IGNITE, CHECK THE OIL TANK FUEL GAUGE. IF THE FUEL GAUGE SHOWS THAT OIL IS PRESENT, PRESS THE RESET B

Page 7 - 6. CHIMNEY VENTING

29733 R2 06/01/2003 15 THE BELT DRIVE COMPONENTS OPERATE AT HIGH SPEEDS AND CAN EASILY SNAG LOOSE CLOTHING, CAUSING SERIOUS PERSONAL INJURY. THIS PR

Page 8

29733 R2 06/01/2003 16B: Annual Service By Contractor THE COMBUSTION CHAMBER (FIREPOT) IS FRAGILE. USE CARE WHEN INSPECTING AND CLEANING THIS AREA

Page 9 - 9. ELECTRICAL CONNECTIONS

29733 R2 06/01/2003 17motor wiring, or replace the fan belt. Finally, restore power to the furnace. E) Operate the furnace through a minimum of th

Page 10 - 12. PIPING INSTALLATION

29733 R2 06/01/2003 18 TABLE A-1 BECKETT AFG OIL BURNER SET-UP BECKETT AFG SERIES OIL BURNERS FURNACE MODEL OUTPUT BTU/Hr BURNER MODEL NOZZLE P

Page 11 - 15. COMBUSTION CHAMBER

29733 R2 06/01/2003 19 TABLE A-3 DIRECT DRIVE BLOWER SET-UP BLOWER SET-UP COOLING CAPACITY 0.20 in. w.c. 0.50 in w.c. FURNACE MODEL BLOWER MOTOR

Page 12 - 17. OIL BURNER SET UP

29733 R2 06/01/2003 2 How to read an Oneida Royal Model Number: HO – B – 120 F B A 4 In the above example, the furnace i

Page 13 - 29733 R2 06/01/2003

29733 R2 06/01/2003 20TABLE A-5 BELT DRIVE BLOWER SET-UP Blower Set-Up Model HO-B 0.20 in. w.c. 0.50 in. w.c. Cooling Capacity Pulley Pulley Bonne

Page 14 - 18. CIRCULATING AIR BLOWER

29733 R2 06/01/2003 21GENERAL DIMENSIONS Table A-6: General Dimensions (inches) Plenum Openings Cabinet Supply Air Return Air Flue Width A Depth B

Page 15 - 19. MAINTENANCE AND SERVICE

29733 R2 06/01/2003 22WIRING DIAGRAM: OIL FURNACE WITH ST9103 EFT & R7184 CONTROL Appendix B WIRING

Page 16

29733 R2 06/01/2003 23WIRING DIAGRAM: OIL FURNACE WITH ST9103 EFT & RIELLO OIL BURNER Appendix B WIRING

Page 17 - 21. OPERATING INSTRUCTIONS

29733 R2 06/01/2003 24WIRING NOTES: HO-B SERIES OIL FURNACE CONTINUOUS FAN OPERATION: The ST9103 EFT has provisions to run the blower motor continuo

Page 18 - Appendix A

29733 R2 06/01/2003 25R7184 DETAILED SEQUENCE OF OPERATION Power is applied to unit. The R7184 completes a self-diagnostic procedure. If no light o

Page 19 - Nominal Values Only

29733 R2 06/01/2003 26 IDLE STATE THERMOSTAT CALLS FOR HEAT SAFETY CHECK FOR FLAME (5 SEC.) BURNER MOTOR & IGNITOR START SOLENOID VALVE OPENS

Page 20

29733 R2 06/01/2003 27 RIELLO 40F3 TROUBLESHOOTING CHART Thermostat is calling for heat, burner is not running.Reset control box. Burner Starts Burn

Page 21 - GENERAL DIMENSIONS

29733 R2 06/01/2003 28 Burner Locks Out After Trial For Ignition · Low resistance or no contact on starting circuit of coil, terminals #2

Page 22 - Appendix B

29733 R2 06/01/2003 29TABLE C-1: ST9103 DETAILED SEQUENCE OF OPERATION Mode Action System Response HEAT Thermostat calls for heat. ("W"

Page 23

29733 R2 06/01/2003 3Table of Contents 1. Introduction...

Page 24 - HO-B SERIES OIL FURNACE

29733 R2 06/01/2003 30 Continued from last page Mode Action System Response Limit switch string opens. (continued) d. Circulating fan runs as long

Page 25 - Appendix C

29733 R2 06/01/2003 31R7184 LED DIAGNOSTIC LIGHT The LED diagnostic light has several functions. It indicates the state or mode in which the oil bur

Page 26 - OPERATION

29733 R2 06/01/2003 32CHECK OIL PRIMARY CONTROL AND IGNITOR If the trouble does not appear to be in the burner or ignition hardware, check the oil p

Page 27 - Burner Does Not Start

29733 R2 06/01/2003 33 · Table C-3: R7184 Troubleshooting continued from previous page Procedure Status Corrective Action Burner starts. Trouble

Page 28

29733 R2 06/01/2003 34 Table C-3: R7184 Troubleshooting continued from previous page Procedure Status Corrective Action Burner starts. Trouble in

Page 29 - Continued on following page

29733 R2 06/01/2003 35 Table C-3: R7184 Troubleshooting continued from previous page Procedure Status Corrective Action Burner locks out. Go to s

Page 30 - Continued from last page

29733 R2 06/01/2003 36 Table C-3: A Troubleshooting continued from previous page. Procedure Status Corrective Action Indicator light is on. Repla

Page 31 - Troubleshooting

29733 R2 06/01/2003 37 TABLE C-4: SYSTEM & GENERAL TROUBLESHOOTING, continued from previous page Problem Possible Cause Remedy No fuel oil. Ch

Page 32

29733 R2 06/01/2003 38 TABLE C-4: SYSTEM & GENERAL TROUBLESHOOTING, continued from previous page Problem Possible Cause Remedy Electrodes out

Page 33 - Continued on next page

29733 R2 06/01/2003 39TABLE C-4: SYSTEM & GENERAL TROUBLESHOOTING, continued from previous page Problem Possible Cause Remedy Airflow blocked

Page 34

29733 R2 06/01/2003 4 1. INTRODUCTION Please read these instructions completely and carefully before installing and operating the furnace. The fur

Page 35

29733 R2 06/01/2003 40HOME OWNER’S REFERENCE TABLE: Installation Contractor: Model No. Serial No. Date Installed Contractor Contact Address

Page 36

29733 R2 06/01/2003 5NOTE: The recommended installation clearances do not take into consideration the clearances necessary to replace the air filter

Page 37

29733 R2 06/01/2003 6NON-SUSPENDED INSTALLATION Maintain clearances to combustibles as outlined in Table 1. Installation on a combustible floor requ

Page 38

29733 R2 06/01/2003 7Figure 2: Common Chimney Problems 6. CHIMNEY VENTING The chimney must be sized correctly and be in good repair. If the chimney

Page 39

29733 R2 06/01/2003 8Table 2: Common Chimney Problems - continued Key Trouble Diagnostic Remedy K Smoke pipe extends into chimney. Measurement of

Page 40 - Oneida Royal Division

29733 R2 06/01/2003 9installed in accordance to the instructions supplied with the regulator. 8. FURNACE CONTROLS The furnace is controlled by eit